Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state certificate shall be displayed in the machine room 5/6/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors No No Cab flooring is loose, protruding above car sill causing trip hazard. 10/13/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display updated Missouri Operating Certificate in machine room 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Elevator car door restrictor does not work, needs repaired. Re-inspection required 5/6/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Elevator car door restrictor needs repaired. Re-inspection required 3/25/2026
MO Minimum : Elevators (A) - Hoistways (A)1 No No Hoistway door non vision panels (sight guards) are missing on the bottom, 5th and 6th floor hoistway doors, needs repaired. 3/25/2026
MO Minimum : Elevators (A) - Hoistways (A)4 No No Hoistway door non vision panels (sight guards) are missing on the bottom, 5th & 6th floor hoistway doors. Need repaired
MO Minimum : Elevators (A) - Hoistways (A)4 No No Hoistway door non vision panels (sight guards) are missing on the bottom, 5th & 6th floor hoistway doors. Need repaired 5/6/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Need to clean dirt, grease and debris from elevator car top 3/25/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required 5/6/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required 3/25/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Need to test phase I and II fire service key. Re-inspection required 3/25/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No No ventilation in machine room. Controllers are in extreme heat, over manufacturers recommendations. 101.5b 10/13/2022
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Phase II fire service operating instructions are missing inside of elevator cab, need to install correct signage 3/25/2026
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Phase II fire service operating instructions are missing inside the elevator cab, need to install correct signage 5/6/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors No No Repair cab floor at opening, it is a tripping hazard 10/13/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are rouged and undersized, need to replace suspension ropes. Re-inspection required 3/25/2026
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)7 Yes Yes The elevator safety governor was found to be worn to a degree that the activation would not set with any sort of consistency. Repair or replacement of the governor is required and a re-inspection shall be performed before the elevator can be returned to service. 11/8/2022