Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Repair cab floor by entrance, it is a tripping hazard
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Violation code 101.5b No ventilation in machine room, controllers are in extreme heat, over manufacturers recommendations
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated Missouri Operating Certificate in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Elevator traction machine is leaking oil. Repair seals and gaskets
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts 8th floor hoistway door interlock electrical cover is missing, replace cover.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase II fire service operating instructions are missing inside elevator cab, need to install correct signage
MO Minimum : Elevators (A) - Hoistways (A)1 Hoistway door non vision panels (sight guards) are missing on the bottom and 3rd floor hoistway doors, needs repaired.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Car flooring is loose, protruding above car sill causing trip hazard.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Multiple hoist ropes do not meet minimum diameter requirements and had several breaks. Replace hoist ropes. Red tagged. 7/16/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Repair car door restrictor. 8/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Elevator cab emergency lights do not work, needs repaired. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Need to test phase I & II fire service. Re-inspection required