A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.3 x x The sprinklers in the pit need to be within 2 ft of the pit floor. NFPA 13 8.15.5.1
A17.1-2016 : Elevators 2.6 - Ventilation 8.11.2.1.2(i) x Complete the installation of the ventilation fan.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide testing of Phase I & II. 11/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide on-site maintenance control program. 10/15/2021