conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car Re levels, oil bleeding through check balve repair or replace machine room control valve.
|
7/3/2018
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Control valve on hydraulic pump unit is leaking hydraulic fluid back into tank. Car sank 3" during 15 minute standing test. Repair and reinspect within THIRTY (30) days
|
4/21/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide on-site maintenance control program.
|
10/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide updated documents.
|
3/14/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Cylinder packing is worn and leaking, repair as needed.
|
3/14/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Provide testing of Phase I &II
|
11/18/2024
|
A17.1-2016 : Elevators
|
11.6 - Temperature/Humidity
|
2.7.9.2
|
x
|
|
Post the temperature and humiodity range for the equipment in the machine room.
|
12/9/2024
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
2.12.7
|
x
|
|
The bottom hoistway access switch does not operate.
|
12/9/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Return to test all initiating devices. The alarm company did not have the code for the fire panel.
|
12/9/2024
|