Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Fire stop on 1st floor hoistway door is missing 4/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Light-ray, door close protection, wired to cab lighting circuit. Move light-ray circuit to proper elevator control circuit. 1/26/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV valve not sealed. Perform OSV test on or before next annual inspection. 10/15/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator phone in cab does not work on 110v emergency power or normal power 1/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Door restrictor does not work 1/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Door restrictor is not working. Re-inspection required 10/11/2023