Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.3.1.2(c) Receptacle in machine room shall be a GFCI. 9/21/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 9/21/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits The pit shall be kept clean and dry. Remove the water from the pit. 9/21/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/21/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be displayed in the elevator machine room. 9/21/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 The machine room door lock needs to be adjusted to properly lock. 9/21/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/15/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light shall be operational. 9/15/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. 9/15/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 The pipes in the machine room shall be guarded or guttered to prevent leakage onto elevator equipment. 9/13/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 Repair the tripping hazard located in front of the controller. 9/13/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/21/2021
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry. Remove water from the pit.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x The overspeed valve is due for category 5 testing. 10/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The rear doors shall be restricted when the car is outside the unlocking zone. 3/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.5 - Normal terminal stopping device 8.11.2.1.3(g) x 8.11.3.1.5(e) - The virtual down directional limit shall stop the car before landing on the buffer. 3/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/3/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) x Machine room door shall be self-locking and self-closing. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x Seal the penetrations in the hoistway. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The front and rear door restrictors shall be operational. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x Repair the plumbing problem in the machine room. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x The existing pipes in the machine room need to be enclosed in a 2 hour fire rated material. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) x At the top and bottom landings, the car doors shall clear the hoistway wall when fully open and operated on hoistway access. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) x Smooth out the machine room floor. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x Flashing fire hat does not flash when required and shall be repaired. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) x Provide an ABC type fire extinguisher in the machine room. 8/14/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) x Secure the old machine room door on the roof to prevent from opened. 8/14/2019