Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Adjust car door restrictor 7/2/2019
MO Minimum : Elevators (I) - Pits (I)1 No No Clean pit 4/6/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Clean pit 12/15/2023
MO Minimum : Elevators (I) - Pits (I)1 Yes No Cleaning of pit not done--failed 1/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Muffler on oil line leaking badly when testing 6/17/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need maintenance control program on site posted on controller 6/17/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform annual test within 30 days 9/28/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service service testing and document on log in machine room 7/30/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 6/7/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 4/6/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 4/6/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 6/7/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 8/20/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 6/17/2020
conversion conversion n/a No No Repair emergency light & bell in car 7/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair emergency phone in car 4/5/2023
conversion conversion n/a No No Repair pit light 7/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Replace backup battery for the phone in car 10/14/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No Test overspeed valve om or before 6/1/23 4/5/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit Red Tagged during overspeed test muffler starting leaking reinspection required 9/28/2022