Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/14/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 6/14/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/27/2020
MO Minimum : Elevators (I) - Pits (I)1 Find and correct source of oil leak in the pit. 10/27/2020
MO Minimum : Elevators (A) - Hoistways (A)13 Holes in front hoistway wall shall be sealed with approved solid material. 10/27/2020
MO Minimum : Elevators (H) - Machine Rooms (H)8 In electrical equipment rooms, the illumination shall not be controlled by automatic means. This switch is currently a motion sensor which could turn off unexpectedly with the technician in the room. 12/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No evacuation procedure in MCP. 12/11/2023
MO Minimum : Elevators (A) - Hoistways (A)16 Remove the unsupported wiring in the hoistway which is not necessary for the operation of the elevator. 10/27/2020
MO Minimum : Elevators (I) - Pits (I)1 Remove water in pit. Take corrective action as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The car top shall be cleaned. 10/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The hoistway shall be cleaned. 10/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The Phase 1 and Phase 2 firefighters key switch bezels shall be legible. 10/27/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. 6/14/2021
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove oil and debris from the elevator pit. 10/27/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and free of dirt and rubbish. 12/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The stop switch bezel shall be legible. 10/27/2020