Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The emergency light shall be operational. 9/9/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency bell shall be operational with 110v source removed. 9/9/2019
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Elevator appears to have a sync issue with jacks (twin post). Correct the sync issue to allow for reliable operation. 9/9/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 1/26/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency lighting shall be operational. 1/7/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm shall be operational. 1/7/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/17/2022
conversion conversion n/a Replace the missing cab ceiling panel. Cab lighting shall be covered. 9/9/2019
conversion conversion n/a Emergency light is not operational. 9/9/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV needs Cat 5 test. 11/10/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The unit was not running at the time of annual inspection. A full annual inspection shall be scheduled for 2020 once the elevator is operational. 10/13/2020