Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) No No Elevator appears to have a sync issue with jacks (twin post). Correct the sync issue to allow for reliable operation. 9/9/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Provide currently serviced fire extinguisher 4/16/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV due for Cat 5 test. 11/9/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work on emergency backup power. Re-inspection required