A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel
|
x
|
|
Phase II operation in car can not be verified because Fire Service Access Panel lock release has been damaged and Key will not turn to access Phase II operation. Must Retest Phase II operation when car panel lock has been replaced.
|
5/22/2023
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
|
|
8.6.4.13.1 front & rear freight car doors shall be repaired and made operational, the doors have been pushed out of alignment to door track guides.
|
10/21/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
8.6.1.6.3 Elevator electrical drawings and testing instructions have become illegible due to water damage.
|
10/21/2024
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)1
|
|
x
|
Car platform and frame have considerable rust damage and some rusted thru spots
|
3/30/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
x
|
All hoistway doors have excessive rust with holes thru
|
3/30/2022
|