conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Alarm bell shall work
|
4/26/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phone should call 24 hrs. monitored number, not a recording
|
4/26/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair inoperable emergency phone
|
8/10/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
No storage in machine room except items related to elevator.
|
10/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Repair leaking pipes and protect equipment from water and moisture.
|
10/1/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not work.
|
10/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Repair leaking pipe in machine room and protect equipment from water and moisture.
|
10/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No maintenance records on site.
|
10/1/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Governor rope is severely rouged and needs to be replaced. Re-inspection required
|
4/8/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Cat 5 test is incomplete. Need to perform the following tests: check governor rope pull through and pull out force. Check tripping speed of car overspeed governor, test car safeties at rated speed with rated load. Test machine brake with 125% of rated load. Re-inspection required
|
4/8/2024
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Governor rope is severely rouged, needs to be replaced. Re-inspection required
|
6/10/2024
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
Install rope data tag on governor rope
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|