MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
6/24/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
5/8/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
No
|
No
|
No equipment shall be added to the machine room or space that is not used in connection with the operation of the elevator. Cable modem, Router, and related equipment to be relocated to outside the Elevator Room.
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
All lamps shall work. Cab lighting shall not be less than 2 lamps and shall develop greater than 5fc at the floor
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone needs to be reprogrammed to contact current service provider.
|
5/6/2024
|