conversion
|
conversion
|
conversion - reinspect
|
x
|
|
all phase I and Phase 2 fire service key switches must be keyed alike in the same building. Key is FEOK1. Reinspection required.
|
11/16/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Clean machine room of all non-elevator parts.
|
12/13/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall not be used for storage of non-elevator equipment.
|
10/1/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
Repair door reopening device.
|
12/13/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Repair machine room door closer.
|
12/13/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Repair machine room door. Should be self-closing, self locking.
|
10/1/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The current state operating certificate needs to be posted in the machine room in a non-combustible frame.
|
3/20/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage and shall be cleaned. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
|
3/20/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing. Repair the door closing device on the machine room door. This item was noted on the previous year report.
|
3/20/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the elevator machine room shall be secured by the manufacturer’s approved device or some other means. The extinguisher cannot be unsecured on he machine room floor.
|
3/20/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The visual signal device did not light in the car when phase I was activated.
|
8/31/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet.
|
3/20/2024
|