Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 DOOR CLOSING FORCE IS >30 LBS 8/12/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 REPAIR HOLE IN MACHINE ROOM CELING WHERE THE SHEETROCK WAS REMOVED TO DO A REPAIR ABOVE THE CELING 8/12/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Car door restrictor does not function 1/5/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not illuminate when normal power for car lights is off. 6/15/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 1/5/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3b Machine room access door needs to be self-closing. 9/22/2020
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate on controller or mainline disconnect. 9/22/2020
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Remove non elevator related material from machine room. Remove trash, rags and flammable items. 9/22/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide test tag for record of annual pressure relief test. 9/22/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers form inside machine room. 9/22/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Install pit collection containers for cylinder drain lines and remove waste oil from pit floor. 11/8/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test firefighters operation monthly and provide log in machine room. 9/22/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly 11/8/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighters instructions next to hall fire keyswitch. 9/22/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighter instructions next to hall fire keyswitch 11/8/2021