Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No The main disconnects, and lighting branch circuit disconnects must have feeder locations labeled. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Yes No The main disconnects and lighting branch circuit disconnects must have feeder locations labeled. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No The machine room lighting shall not be less than 19fc at the floor level. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Yes No The machine room lighting shall not be less than 19fc at the floor level. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Yes No The machine room lighting shall be guarded. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No The machine room lighting shall be guarded. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Yes No The machine room lighting shall be enclosed. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No Standby/emergency power operation of the elevator shall be tested. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) No No Seal all penetrations in the hoistway. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) Yes No Seal all penetrations in the hoistway. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No Provide at least one GFCI duplex receptacle in the machine room. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Yes No Provide at least one GFCI duplex receptacle in the machine room. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Yes No Provide a current ABC type fire extinguisher in the machine room. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) No No Provide a current ABC type fire extinguisher in the machine room. 9/27/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In car emergency telephone shall work. 8/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No Fire service operation shall be tested along with all initiating devices. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes Fire Fighters operation must be tested, including all recall and shunt trip devices, and an indicator light is required at the egress floor. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) No No Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) Yes No Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power must be tested annually. 7/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 11/15/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 3/17/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 Yes No Counterweight displacement function shall be operational. 3/3/2020
conversion conversion n/a No No Car emergency lighting shall work. 6/1/2018
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Building is currently under construction. About 50 feet of the hoistway shall be completed with approved materials. 11/15/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 Yes No An identified momentary reset button or switch for each elevator, shall be located in the control panel in the elevator machine room for the counterweight displacement function. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Yes No All wireway and electrical device covers shall be installed. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) No No All wireway and electrical device covers shall be installed. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) No No All temporary wiring shall be removed. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Yes No All temporary wiring shall be removed. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) No No All machine room wiring shall be enclosed. 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes A fire service indicator light is required at the egress floor. Unit undergoing MOD and not in service 4/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 8.6.4.11 Yes No 2.10.2.2 - An intermediate rail, member, or panel is required on the standard car top railing. 4/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 8.6.4.11 Yes No 2.10.2.2 - An intermediate rail, member, or panel is required on the standard car top railing. 3/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) The main disconnects, and lighting branch circuit disconnects must have feeder locations labeled. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) The machine room lighting shall not be less than 19fc at the floor level and the machine room lighting shall be guarded. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) Seal all penetrations in the hoistway. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) Provide at least one GFCI duplex receptacle in the machine room. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) Provide a current ABC type fire extinguisher in the machine room. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) All machine room wiring shall be enclosed, all wireway and electrical device covers shall be installed, and all temporary wiring shall be removed. 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) A fire service indicator light is required at the egress floor. Unit undergoing MOD and not in service 4/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No (Acceptance violations that need to be re-inspected) 2.10.2.2 - An intermediate rail, member, or panel is required on the standard car top railing. 4/29/2022