Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 8/29/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency lighting shall work. 11/11/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency lighting shall be operational. 11/25/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power must be tested annually. 7/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 11/9/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power must be tested annually. (Scheduled for 11/15/23) 11/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The building work in progress includes a remote fire control panel. When work is complete, the tests and requirements of A17.2 item 6.4, A17.1-2005 - 8.10.2.2.6 shall apply. 11/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The building work in progress includes running some or all of the elevators in this group under standby emergency power. When work is complete, the tests and requirements of A17.2 items 1.17 & 4.12, A17.1-2005 - 8.10.2.2 shall apply. 11/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The building work in progress includes running some or all of the elevators in this group under standby emergency power. When work is complete, the tests and requirements of A17.2 items 1.17 & 4.12, A17.1-2005 - 8.10.2.2 shall apply. 12/13/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The building work in progress includes a remote fire control panel. When work is complete, the tests and requirements of A17.2 item 6.4, A17.1-2005 - 8.10.2.2.6 shall apply. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide at least one GFCI duplex receptacle in the machine room. 9/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) x Provide at least one GFCI duplex receptacle in the machine room. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 9/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 9/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) x Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Provide a current ABC type fire extinguisher in the machine room. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x All machine room wiring shall be enclosed. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x All wireway and electrical device covers shall be installed. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x All temporary wiring shall be removed. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 All machine room wiring shall be enclosed. 9/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.9 - Guarding of exposed auxiliary equipment 8.11.2.1.2(i) x Machine guards shall be in place. 12/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 8.11.2.1.4(a) x The platform guard (apron) is 39.5" and should be 48". The pit is of inadequate depth to support a 48" toe guard. Variance may be required. 12/13/2021
conversion conversion n/a Car emergency lighting shall work. 6/1/2018