Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Door restrictor does not work. Repair 12/4/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Braille floor identification is missing on 1st and 3rd floor 4/30/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Yes Yes Car buffer stands are rusted out and buffers are laying on the pit floor. Counterweight buffers mounitng channels are rusted and need to be replaced. Red-tagged, Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lighting shall be repaired or replaced 4/30/2026
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are below minimum diameter. Replace. 12/4/2018
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required