MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
Braille floor identification is missing on 1st and 3rd floor
|
4/30/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
Yes
|
Yes
|
Car buffer stands are rusted out and buffers are laying on the pit floor. Counterweight buffers mounitng channels are rusted and need to be replaced. Red-tagged, Re-inspection required
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
Yes
|
No
|
Door restrictor does not work. Repair
|
12/4/2018
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
Machine room lighting shall be repaired or replaced
|
4/30/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Need to test elevator for operation on emergency power. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Suspension ropes are below minimum diameter. Replace.
|
12/4/2018
|