Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/16/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be displayed in the elevator machine room. 5/16/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall be operational. 11/30/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) No No Clean the car top. 6/1/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No The pit shall be kept clean. Remove excess debris from pit. 6/1/2023
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Machine room shall have a proper fire extinguisher and shall have current test tag. 6/1/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No MCP fire service testing shall be properly documented monthly on log sheet. 6/1/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Note: Last entry 3/2022, no annual test documents. 4/1/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No No The machine room shall be kept clean. There is a lot of lint on everything. 4/1/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be operational. 5/28/2025
conversion conversion conversion - reinspect Yes No In cab emergency telephone shall work. 5/17/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Replace damaged door guide at first floor. There is a loud, scraping noise. 3/17/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Replace damaged door guide at first floor. There is a loud, scraping noise. 6/1/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/20/2022