Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 9/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.3.2 x A category 5 full load test shall be scheduled in the 2019 calendar year. 9/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.2.3.1 x x A category 5 full load test shall be scheduled in the 2019 calendar year. 9/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.11.2.3.6 x A category 5 full load test shall be scheduled in the 2019 calendar year. 9/23/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 8.11.2.1.3(z) Provide shortening of the governor rope. 2/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone does not work. Initiate the necessary corrective action. 12/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(k) The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 1/5/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.27 - Rope fastenings 8.11.2.1.2(y) The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 1/5/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/26/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP, including PM records and monthly fire service test log, not being properly documented. 2/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and related on-site documentation shall be provided in the machine room. 2022 MCP records are missing. 2/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 Suspension rope tensions shall be substantially equalized. 2/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Remove excess debris. 2/28/2024