ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
The fire extinguisher in the machine room is expired and shall be replace or serviced.
|
2/28/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
The machine room vent shall be provided with a cover.
|
2/28/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
8.11.2.1.2(d)
|
|
|
Seal all machine room penetrations.
|
2/28/2020
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
|
1/5/2022
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
1001.2(b)(11)
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
1/5/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Replace the missing machine room door knob. Must be self-locking type.
|
2/28/2020
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.2
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. Relocate security system from machine room.
|
2/3/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up to date operating certificate is required in machine room.
|
2/3/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP, including PM records and monthly fire service test log, not being properly documented.
|
2/28/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Front pit sump pump appears to not be working.
|
2/28/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing/damaged pickup rollers.
|
2/28/2024
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
|
2/28/2024
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
111
|
|
|
Hoistway doors at floor one need to be adjusted/repaired. Gap approximately 2.5". (Bi-parting freight doors)
|
2/28/2024
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and related on-site documentation shall be provided in the machine room. 2022 MCP records are missing.
|
2/28/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work. Main COP ADA/Help phone is not working. AUX COP handset phone does work. Where emergency phones are provided they shall be operational.
|
2/23/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational with 24/7 support.
|
2/6/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency phone does not work. Initiate the necessary corrective action.
|
12/28/2021
|