A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
102
|
x
|
|
the outlet for the pit sump pump shall not be of the GFCI type and on a seperate branch circuit from the GFCI outet and pit light
|
5/15/2020
|
A17.1-1996 : Elevators
|
1.4 - Sills and car floor
|
110.13a
|
|
|
Replace broken tile in front of top landing sill (trip hazard)
|
9/1/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post a log in the machine room
|
9/1/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
monthly fire service test log is not being filled out monthly
|
11/4/2021
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
a new copy of the state operating certificate is to be posted in the machine room
|
11/4/2021
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
pit light has been disconnected from building power, the light switch is to be accessible from the landing
|
11/4/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Group 2 door lock needed to prevent access by school children
|
11/20/2024
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)4
|
|
|
Provide crosshead data tag
|
11/20/2024
|