Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.4 - Sills and car floor 110.13a Replace broken tile in front of top landing sill (trip hazard) 9/1/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service test and post a log in the machine room 9/1/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log is not being filled out monthly 11/4/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a new copy of the state operating certificate is to be posted in the machine room 11/4/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) pit light has been disconnected from building power, the light switch is to be accessible from the landing 11/4/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Group 2 door lock needed to prevent access by school children 11/20/2024
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 Provide crosshead data tag 11/20/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 x the outlet for the pit sump pump shall not be of the GFCI type and on a seperate branch circuit from the GFCI outet and pit light 5/15/2020