Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 9/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track (floor 1 & 4). 9/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track (floor 1 & 4). Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 9/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates COP shall have car number displayed (multiple units onsite). 9/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates COP shall have car number displayed (multiple units onsite). Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly. 9/26/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly. Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 Repair machine room smoke detector, damaged and hanging by its wiring. 9/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 Repair machine room smoke detector, damaged and hanging by its wiring. Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Top emergency exit shall be properly secured. 9/26/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Top emergency exit shall be properly secured. Not verified during phone reinspection. Owner to self-certify. 10/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. 9/26/2025