Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Monthly firefighters service logs shall be maintained on site 5/25/2022
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 1001.2(c)(15) Doors need to have stenciling labeling correct floor 5/25/2022
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Top floor is missing a door gib 5/25/2022
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) Fill hole in hoistway making hoistway completely enclosed 5/25/2022
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x x Suspension ropes are undersized with rouge. RED TAGGED 9/22/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 x Monthly firefighters logs shall be maintained on site 9/22/2021
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) x Top floor door is missing door gib 9/22/2021
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 1001.2(c)(15) x Door needs to have stenciling labeling of correct floor 9/22/2021
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) x Fill hole in hoistway making hoistway fully closed 9/22/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Monthly firefighters service logs shall be maintained on site 3/25/2022
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) Fill hole in hoistway making hoistway completely enclosed 3/25/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current certificate on display. 7/17/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Replace top floor door restrictor bracket. 7/2/2020
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV must have a cat 5 weight test performed within 90 days or less 9/22/2021
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 3/25/2022
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x OSV needs to be tested with full load within 90 days 9/22/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. 8/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The hoistway door at the 3rd landing is not self-closing/self-locking. The hoistway door shall be adjusted. 8/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems A door retaining gib is missing on the 2nd floor hoistway door, a replacement door gib shall be installed. 8/9/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate shall be posted in the machine room in a non-combustible frame. 8/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The hoistway door at the 3rd landing is not self-closing/ self-locking. The hoistway door shall be adjusted. 8/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems A door retaining gib is missing on the 2nd floor hoistway door, a replacement door gib shall be installed. 8/23/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate shall be posted in the machine room in a non-combustible frame. 8/23/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room. 8/22/2023