Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(G)
|
|
|
Needs step indexing test.
|
7/17/2019
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.1 Escalator Handrails
|
|
|
Repair handrail inlets at bottom of escalator.
|
3/23/2020
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.2 Escalator Step-to-Skirt Clearance
|
x
|
|
Re-adjust left skirt seam joint back to flush state. 8.6.8.3
|
6/23/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing is incomplete, need to test brake torque, safety switches, comb plate impact switches, missing step switches & hand rail speed sensor. Re-inspection required
|
9/5/2024
|
Missouri Minimum : Escalators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Comb impact test failed, adjust as needed.
|
|
Missouri Minimum : Escalators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Step indexing test failed, adjust as needed.
|
|
A17.1-2016 : Elevators
|
8.13 - Handrail systems and safety devices
|
8.6.8.15.13
|
|
|
The handrail inlet switches on the bottom landing do not operate as intended. Repair or replace
|
3/21/2022
|
A17.1-2016 : Elevators
|
8.3 - Controller and wiring
|
8.6.8.15.3
|
|
|
Replace cover on main control box.
|
11/3/2020
|
A17.1-2016 : Elevators
|
8.8 - Broken step chain device
|
8.6.8.15.8
|
|
x
|
The carriage switch on both sides of the bottom landing do not stop the escalator when actuated. Repair or replace
|
3/2/2022
|