MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the escalator at this time. The brake, handrail inlet, and comb impacts tested before the inspection is completed.
|
11/17/2023
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(G)
|
|
|
Step indexing test needs to be conducted.
|
7/17/2019
|
A17.1-2016 : Elevators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
6.1.7
|
x
|
|
Provide code compliant pit lighting, both ends.
|
|
A17.1-2016 : Elevators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
6.1.7
|
x
|
|
Provide code compliant duplex receptacle in each pit.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.14 Escalator Entrance and Egress Ends
|
|
|
Left skirt too tacky to perform indexing properly. Clean unknown fluid off of skirts. 8.6.8.3
|
11/3/2020
|
A17.1-2016 : Elevators
|
8.3 - Controller and wiring
|
8.6.8.15.3
|
|
|
Replace cover on main control box.
|
11/3/2020
|