Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the escalator at this time. The brake, handrail inlet, and comb impacts tested before the inspection is completed. 11/17/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(G) Step indexing test needs to be conducted. 7/17/2019
A17.1-2016 : Elevators 8.1 - Machinery space access, lighting, receptacle, and condition 6.1.7 x Provide code compliant pit lighting, both ends.
A17.1-2016 : Elevators 8.1 - Machinery space access, lighting, receptacle, and condition 6.1.7 x Provide code compliant duplex receptacle in each pit.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Escalator Entrance and Egress Ends Left skirt too tacky to perform indexing properly. Clean unknown fluid off of skirts. 8.6.8.3 11/3/2020
A17.1-2016 : Elevators 8.3 - Controller and wiring 8.6.8.15.3 Replace cover on main control box. 11/3/2020