Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Escalator Entrance and Egress Ends Multiple end caps by the handrail inlets are missing and shall be replaced. 7/27/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.3 Step/Skirt Performance Index x Need to repair right side skirt so skirt step indexing can be performed to complete inspection. Re-inspection required 11/1/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(D) Repair step chain on left side (required repair within 60 days) 7/17/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(G) Need to perform step indexing test. 7/17/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The inspection is not completed at this time. The top landing comb impact devices shall be tested before the inspection is completed. 3/6/2023
A17.1-2016 : Elevators 8.1 - Machinery space access, lighting, receptacle, and condition 6.1.7 x Provide code compliant pit lighting, both ends.
A17.1-2016 : Elevators 8.1 - Machinery space access, lighting, receptacle, and condition 6.1.7 x Provide duplex receptacle in each pit.