A17.1-2016 : Elevators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
6.1.7
|
x
|
|
Provide code compliant pit lighting, both ends.
|
|
A17.1-2016 : Elevators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
6.1.7
|
x
|
|
Provide duplex receptacle in each pit.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(D)
|
|
|
Repair step chain on left side (required repair within 60 days)
|
7/17/2019
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(G)
|
|
|
Need to perform step indexing test.
|
7/17/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The inspection is not completed at this time. The top landing comb impact devices shall be tested before the inspection is completed.
|
3/6/2023
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.14 Escalator Entrance and Egress Ends
|
|
|
Multiple end caps by the handrail inlets are missing and shall be replaced.
|
7/27/2023
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.3 Step/Skirt Performance Index
|
x
|
|
Need to repair right side skirt so skirt step indexing can be performed to complete inspection. Re-inspection required
|
11/1/2023
|