Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A fire extinguisher shall be placed in machine room that has been serviced and has a current inspection tag 12/1/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting shall be not less than 10 foot candles at the floor 12/1/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Means of two-way communication are inoperable and shall be repaired or replaced.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit stopped operating during testing. Performed testing of car buffer, full load counterweight buffer, full load speed safeties including slide, fire service, 125% brake, emergency light, alarm and phone and door closing force. Re-inspection required 11/18/2022