MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit stopped operating during testing. Performed testing of car buffer, full load counterweight buffer, full load speed safeties including slide, fire service, 125% brake, emergency light, alarm and phone and door closing force. Re-inspection required
|
11/18/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Means of two-way communication are inoperable and shall be repaired or replaced.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting shall be not less than 10 foot candles at the floor
|
12/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A fire extinguisher shall be placed in machine room that has been serviced and has a current inspection tag
|
12/1/2023
|