MO Minimum : Elevators
|
11 CSR 40-5.130 Variances
|
(2)(B) Variance Inspection
|
|
|
Variance Inspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Supply equipment necessary to perform the safety test on the slack cable safeties
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Replace defective hoist cables. Red tagged, Re-inspection required
|
5/7/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.18.3 Key-Operated Switches
|
|
|
Hall buttons shall be operated by a key switch with key removable in off position only.
|
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.19.1 Two-Way Communications Means
|
x
|
|
No emergency phone in elevator.
|
5/7/2024
|
A17.1-2016: Residential
|
5.3.1 Private Residence Electric Elevators
|
5.3.1.8.3 Clearance Between Hoistway Doors and Car Doors or Gates
|
x
|
x
|
Door spacers do not meet the current 3/4' and 4' code requirement.
|
5/7/2024
|