MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire service phase 2 problem the elevator will not return automatically to return floor when key SW is tirned to off. Repair must be completed within 14 calendar days or elevator must be removed from service
|
7/6/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
x
|
|
Phase I fire fighters key switch at first level failed to operate, no proper keys. Re-inspection required
|
4/26/2024
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
x
|
|
Minimum of two car lamps required. Re-inspection required
|
4/26/2024
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
x
|
|
Car lighting is required to be protected against accidental contact and in a manner capable of containing broken glass. Re-inspection required
|
4/26/2024
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
No Emergency Light
|
6/5/2019
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.2
|
|
|
No storage In Machine Room
|
6/5/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
Phase 1 Fire Service only
|