MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Top door missing door gib. REINSPECT REQUIRED
|
8/23/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Bottom door is missing 2 gibs and a 3rd is barely there causing a 1 1/8 inch gap. REINSPECT REQUIRED
|
8/23/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Suspension ropes are undersized with rouge,
|
8/23/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Monthly fire log not up to date
|
3/30/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Monthly firefighters service logs shall be maintained on site
|
3/20/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV needs to be tested with full load within 90 days or less. REINSPECT REQUIRED
|
3/20/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV needs to be tested with full load within 90 days or less
|
3/30/2022
|