MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The overspeed valve shall be repaired/replaced and fireman’s service tested before the inspection is completed.
|
12/22/2022
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Repair lights in machine room.
|
7/17/2019
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Bad hoist cable needs to be replaced.
|
10/25/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required.
|
12/22/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve (Red Tag)
|
x
|
x
|
The overspeed valve device failed to activate on this elevator in overspeed conditions with a rated load. The valve shall be repaired/replaced and a reinspection performed before the elevator can be returned to operational service.
|
12/22/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Must test OSV this year
|
11/10/2022
|