Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The machine room illumination shall be not less than 10fc at the floor level at the controller. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The machine room shall have a proper ABC fire extinguisher and shall have a current monthly/annual test tag. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x There are 2 LB electrical box covers missing in the machine room. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The machine room disconnects shall be labeled with location of feed breakers and purpose (elevator). 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Fire caulk/fill holes and voids in hoistway walls around hall station "flex" 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Cut off exposed drywall screws from hoistway. Currently cutting hazard for workers. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Adjust top floor hoistway access lower limit, cartop to stop level with landing sill. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Plunger packing blew out during stop ring test. Replace and redo stop ring test to verify. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Install smoke detector at 2nd floor landing. 10/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Test all FAID for function and recall operations (with smoke/heat, no magnet). 10/8/2025