Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x x Door opens automatically on Phase II fire service. Red tagged, Re-inspection required 11/23/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Telephone in car doesn't work Phone line dead to controller 7/1/2019
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Increase the machine room illumination to 10ft candles as required 12/15/2021
A17.1-1996 : Elevators 2.31 - Relief Valves 1006.2b Need to obtain relief valve pressure on reinspection. Annual inspection incomplete. 8/26/2019
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and shall be tested within 90 days or less 11/17/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Repair phase 2 fire recall door does not remain closed after closing. Door auto opens after going to the floor in phase 2 11/17/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state certificate shall be displayed. 9/11/2019