A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Telephone in car doesn't work Phone line dead to controller
|
7/1/2019
|
A17.1-1996 : Elevators
|
2.31 - Relief Valves
|
1006.2b
|
|
|
Need to obtain relief valve pressure on reinspection. Annual inspection incomplete.
|
8/26/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state certificate shall be displayed.
|
9/11/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
Repair phase 2 fire recall door does not remain closed after closing. Door auto opens after going to the floor in phase 2
|
11/17/2022
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Increase the machine room illumination to 10ft candles as required
|
12/15/2021
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed and shall be tested within 90 days or less
|
11/17/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
Door opens automatically on Phase II fire service. Red tagged, Re-inspection required
|
11/23/2022
|