A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency battery lowering device is not working, needs repaired. Re-inspection required
|
2/28/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work, possibly no phone line. Re-inspection required
|
2/28/2023
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Perform OSV test on or before next annual inspection date.
|
4/22/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Both cylinder head packing collection lines go directly back into hydraulic tank. Oil loss cannot be monitored in this configuration. Need to install collection buckets in elevator pit to monitor amount of oil loss that has occurred.
|
|