| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements |  |  | The fire extinguisher in the machine room is expired and shall be serviced (Expired 2016). |  | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)2 |  |  | The machine room door shall be self-closing. |  | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | Display current state operating certificate. |  | 
                
                    | MO Minimum : Elevators | (A) - Hoistways | (A)8 |  |  | Egress at the 7th floor shall not be blocked by door. |  | 
                
                    | MO Minimum : Elevators | (A) - Hoistways | (A)17 |  |  | Pipes conveying liquids are not allowed in the hoistway. |  | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)1 |  |  | The pit shall be kept clean and dry. |  | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)2 |  |  | The buffers in the pit show signs of water submersion. Verify that the buffer oil has not been contaminated. |  | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)3 |  |  | Counterweight guard shall not extend more than 12" above the pit floor. |  | 
                
                    | MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting |  |  | Emergency lights shall be operational. |  | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)2 |  |  | The machine room shall have a self-closing and self-locking door and shall operable from the interior space without the use of a key. |  | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |  | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)3 |  |  | The counterweight guard shall extend from a point not more than 12" above the pit floor. |  | 
                
                    | MO Minimum : Elevators | (A) - Hoistways | (A)16 |  |  | The broken piece of flexible wireway feeding the down slowdown in the pit shall be replaced. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods |  |  | The traveling cable shall be re-hung where it does not rub against the pit wall. |  | 
                
                    | MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting |  |  | The in car lighting shall be guarded. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods |  |  | The car top light shall be guarded. |  | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers |  |  | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records |  |  | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) |  | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |  | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)2 |  |  | The machine room shall have a self-closing and self-locking door and shall operable from the interior space without the use of a key. |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x |  | Emergency lights shall be operational. | 3/8/2023 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x |  | Emergency light is not working. Re-inspection required | 10/2/2023 | 
                
                    | MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x |  | Need to perform full load buffer test. Buffers need cleaned of rust. Re-inspection required | 10/2/2023 | 
                
                    | MO Minimum : Elevators | (I) - Pits | (I)2 | x | x | Repair or replace defective car and counterweight buffers. Red-tagged, Re-inspection required |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x |  | The emergency lights shall be operational. | 8/25/2021 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x |  | The in car emergency telephone shall be operational on auxiliary power. | 8/25/2021 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x |  | The emergency lights shall be operational. | 8/25/2021 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x |  | The alarm bell shall be operational on auxiliary power. | 8/25/2021 | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | (S)1 | x |  | In car emergency stop switch shall be overridden on Phase 1 fire service. | 2/10/2020 |