MO Minimum : Elevators
|
(A) - Hoistways
|
(A)17
|
|
|
Pipes conveying liquid are not permitted in the hoistway.
|
3/18/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)8
|
|
|
Egress shall not be blocked by door at 7th floor.
|
3/18/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)17
|
|
|
Pipes conveying liquids, gases, or vapors shall not be located in the hoistway. The copper pipe in the overhead shall be removed.
|
3/18/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed that shall be replaced.
|
3/18/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hoistways containing passenger elevators shall be fully enclosed and the enclose shall be of a solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired.
|
3/18/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)17
|
|
|
No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)17
|
|
|
No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The in car lighting shall be guarded.
|
3/18/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The counterweight is compressing the buffer with the car level at the top landing. Counterweight runby shall be provided.
|
3/18/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency telephone shall be operational on auxiliary power.
|
8/25/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair the pit lighting.
|
3/18/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
The fire extinguisher in the machine room shall be serviced (Expired 2016).
|
3/18/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing.
|
3/18/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room shall have a self-closing and self-locking door and shall operable from the interior space without the use of a key.
|
3/18/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)3
|
|
|
The counterweight guard shall extend from a point not more than 12" above the pit floor.
|
3/18/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit lighting shall be operational.
|
3/18/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water and oil shall not be allowed to accumulate on pit floors. Note: The pit has at least 1 foot of standing water in it.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
x
|
x
|
Repair or replace defective car and counterweight buffers. Red-tagged, Re-inspection required
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
A hoist rope tag shall be provided.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
A hoist rope tag shall be provided.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
A hoist rope tag shall be provided.
|
3/18/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase 2 fire service shall be operational. (Violation to be corrected no later than April 17th, 2020.
|
8/25/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
In car emergency stop switch shall be overridden on Phase 1 fire service.
|
2/10/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
(A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced.
|
3/9/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The car and counterweight buffer switches shall be operational.
|
3/9/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Needs annual test completed after cleaning and removing rust from pistons. Re-inspection required
|
10/2/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
(A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced.
|
8/25/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The car and counterweight buffer switches shall be operational.
|
8/25/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The car and counterweight buffer switches shall be operational.
|
8/25/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/18/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
3/18/2021
|