Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The car and counterweight buffer switches shall be operational. 8/25/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x (A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced. 8/25/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The car and counterweight buffer switches shall be operational. 8/25/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x (A-16) - The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed. It shall be replaced. 3/9/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The car and counterweight buffer switches shall be operational. 3/9/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Needs annual test completed after cleaning and removing rust from pistons. Re-inspection required 10/2/2023
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired.
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired.
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistways containing passenger elevators shall be fully enclosed and the enclose shall be of a solid construction. The large hole through the back hoistway wall in the pit looking into a restroom shall be repaired. 3/18/2021
MO Minimum : Elevators (A) - Hoistways (A)16 The wireway feeding the car and counterweight buffer switches has rusted away and has energized wires exposed that shall be replaced. 3/18/2021
MO Minimum : Elevators (A) - Hoistways (A)17 Pipes conveying liquids, gases, or vapors shall not be located in the hoistway. The copper pipe in the overhead shall be removed. 3/18/2021
MO Minimum : Elevators (A) - Hoistways (A)17 Pipes conveying liquid are not permitted in the hoistway. 3/18/2021
MO Minimum : Elevators (A) - Hoistways (A)17 No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed.
MO Minimum : Elevators (A) - Hoistways (A)17 No pipes conveying liquids, gases, or vapors shall be located in the hoistway. The copper pipe in the overhead shall be removed.
MO Minimum : Elevators (A) - Hoistways (A)8 Egress shall not be blocked by door at 7th floor. 3/18/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The in car lighting shall be guarded. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational on auxiliary power. 8/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair the pit lighting. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The fire extinguisher in the machine room shall be serviced (Expired 2016). 3/18/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing. 3/18/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room shall have a self-closing and self-locking door and shall operable from the interior space without the use of a key. 3/18/2021
MO Minimum : Elevators (I) - Pits (I)1 Water and oil shall not be allowed to accumulate on pit floors. Note: The pit has at least 1 foot of standing water in it.
MO Minimum : Elevators (I) - Pits (I)2 x x Repair or replace defective car and counterweight buffers. Red-tagged, Re-inspection required
MO Minimum : Elevators (I) - Pits (I)3 The counterweight guard shall extend from a point not more than 12" above the pit floor. 3/18/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational. 3/18/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) A hoist rope tag shall be provided. 3/18/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) A hoist rope tag shall be provided.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) A hoist rope tag shall be provided.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase 2 fire service shall be operational. (Violation to be corrected no later than April 17th, 2020. 8/25/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x In car emergency stop switch shall be overridden on Phase 1 fire service. 2/10/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/18/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 3/18/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The counterweight is compressing the buffer with the car level at the top landing. Counterweight runby shall be provided. 3/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.