MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Debris in pit.
|
8/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Handrail loose in car.
|
8/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Handrail missing in car.
|
8/1/2023
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.14.2 Hydraulic Cylinders and Pressure Piping
|
x
|
x
|
leak down test failed dropped 2 inches in 15 mins futher testing required no shutoff valve
|
10/23/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
mach. room door lock defeatable
|
10/24/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
machine room door not self locking provide self looking door handle
|
8/25/2023
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)9
|
|
|
Main line disconnect has broken component inside, replace disconnect switch in machine room.
|
8/1/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt displayed
|
10/24/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not working not answered
|
10/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Position indicator on COP not displaying floor numbers.
|
8/1/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
8/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Provide a 5 gallon pit jug in pit to collect leakage from jack packing.
|
8/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide an MCP in machine room to log maintenance, repairs, and inspections.
|
8/1/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove sprinkler head from ceiling above controller, no heat detector or shunt trip present.
|
8/1/2023
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
Stop switch on car operating panel worn, and not legible. Replace
|
8/23/2023
|