Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No Repair emergency lights in car. 11/5/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Emergency light not working. 12/11/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency light (still) inoperative. 3/10/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency light and alarm bell do not work. 3/28/2022
A17.1-1996 : Elevators 2.17 - Drive machine brake 1001.2(b)(15) Yes Yes Car lowered, stopped and held 125% capacity, however adjustment needs to be made for brake pick gaps to a consistent .005 as per brake data tag. Reinspection only. 3/28/2022
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) No No Repair or replace travel cable due to damage and/or breakage of cable insulation at basement floor loop 11/5/2025
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) No No Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop 11/5/2025
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) No No Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop 3/11/2026
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) Yes No Repair/replace travel cable due to damage and/or breakage of cable insulation. Basement floor loop
A17.1-1996 : Elevators 3.22 - Wire rope fastening and hitch plate 1001.2(c)(28) No No Replace anti-rotation devices on counterweights. 11/5/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Repair pit light. 11/5/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the elevator machine room 11/5/2025