Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair cab steadier on top of car, cab is not sturdy 9/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair cab steadier on top of car, cab is not sturdy. (could not confirm) 10/16/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 10/16/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone does not connect to 24x7 security. 3/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x This unit has not had a documented annual inspection performed since 3/28/22 and the last category 5 test was 3/5/2018. This elevator shall have a full category 5 test completed within 15 days. Failure to comply in this time frame will result in the elevator placed out of service with a red tag issued. Only a machine room inspection has been performed at this time. 10/16/2025
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b x The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. This currently is an unsafe condition as temporary means of keeping the machine room space cool has resulted in the equipment being open to the elements. Reinspection is required. 10/16/2025
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 210.2(h) Car top switch on door operator is broken. Repair (could not confirm) 10/16/2025
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 210.2(h) Car top switch on door operator is broken. Repair 9/30/2025
A17.1-1996 : Elevators 3.23 - Suspension rope 212 x Suspension ropes are crossed and are impinging on rope pocket/machine room floor. 1/14/2020
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 202 x Counterweight siesmic displacement detection does not open door. 1/14/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the elevator machine room 9/30/2025