MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a maintenance control program on site
|
5/11/2021
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
REMOVE WATER FROM THE PLIT. MEANS SHOULD BE PROVIDED TO PREVENT ACCUMULATION OF THE WATER.
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.11
|
|
|
REPLACE NORTH LEAKING JACK PACKING
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
x
|
|
TEST OVERSPEED VALVE (UNSEALED). REINSPECTION REQUIRED WITHIN 30 DAYS
|
|
A17.1-2016 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.11.1 Firefighters’ Emergency Operation
|
x
|
|
REPAIR PHASE 2 FIRE SERVICE OPERATION. PHAS 2 DOES NOT OVER RIDE KEYED OUT FLOOR SWITCHES. REINSPECTION REQUIRED WITHIN 30 DAYS.
|
|