Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x Auxiliary power lowering unit (emergency rescue unit) does not work. Power supply has not been removed. Elevator controller has wiring and circuit board for emergency rescue unit. Also needs auxiliary contacts installed in mainline disconnect for proper operation, needs repaired. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, phone line has no power. Re-inspection required