Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Full load slide test failed unit red tagged out of service
conversion conversion n/a Firefighters Phase II instructions needs to be legible 8/17/2018
conversion conversion n/a Pit ladder is not safely accessible 8/17/2018
conversion conversion n/a Car top needs to be cleaned 8/17/2018
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 3/29/2021
MO Minimum : Elevators (I) - Pits (I)1 Remove water from pit 3/29/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair fire service phase II operation 8/23/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire Service Phase 2 still down 9/28/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair phase 2 fire service when tuened off in the car, it returns to the first floor and the car doors do not open and car does not return to phase 1 8/31/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x x Reinspection checking phase 2 Fire service. No repairs made red tagged unit. 9/26/2023