conversion
|
conversion
|
n/a
|
|
|
Firefighters Phase II instructions needs to be legible
|
8/17/2018
|
conversion
|
conversion
|
n/a
|
|
|
Pit ladder is not safely accessible
|
8/17/2018
|
conversion
|
conversion
|
n/a
|
|
|
Car top needs to be cleaned
|
8/17/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log in machine room
|
3/29/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water from pit
|
3/29/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair fire service phase II operation
|
8/23/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire Service Phase 2 still down
|
9/28/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log in machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair phase 2 fire service when tuened off in the car, it returns to the first floor and the car doors do not open and car does not return to phase 1
|
8/31/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
Reinspection checking phase 2 Fire service. No repairs made red tagged unit.
|
9/26/2023
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Full load slide test failed unit red tagged out of service
|
|