Car top needs to be cleaned
|
8/17/2018
|
conversion
|
conversion
|
n/a
|
|
|
Firefighters Phase II instructions needs to be legible
|
8/17/2018
|
conversion
|
conversion
|
n/a
|
|
|
Pit ladder is not safely accessible
|
8/17/2018
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service Phase 1 & 2 need to be tested when remaining units are tested. It is also unknown if the elevators operate on an emergency generator. If this unit is equipped to operate on the emergency generator, it shall be tested.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire Service Phase 2 still down
|
9/28/2021
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Full load slide test failed unit red tagged out of service
|
1/30/2025
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log in machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log in machine room
|
3/29/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
Reinspection checking phase 2 Fire service. No repairs made red tagged unit.
|
9/26/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water from pit
|
3/29/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair fire service phase II operation
|
8/23/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair phase 2 fire service when tuened off in the car, it returns to the first floor and the car doors do not open and car does not return to phase 1
|
8/31/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing incomplete: Only tested slide & smashed car buffer, problems with running equipment. The annual inspection and category 5 testing shall be completed. Note: Unit remains locked out of service until category 5 testing is completed as slide was cited as non-compliant in 2023.
|
2/15/2025
|